Acuvim II Power Meter with Available Data Logging
- Power Meter with Datalogging Records Voltage, Current, Amperage, Frequency, Power (Reactive, Apparent, Active), Energy, Power Factor, Peak Demand, Run Time, THD and Individual Harmonics
- 16 Different Alarm Parameters for Alerts
- Various I/O Modules Available for Digital Inputs/Outputs, Analog Inputs/Outputs and Relay Outputs
- Compatible with Single or Three-Phase Electrical Systems up to 600 Volts AC
- View Data and Charts Online in a Browser and Receive Email Notifications with Optional Ethernet Communications Module
- Modbus, WiFi, Ethernet and Profibus Communication Ports Available
- New! Free AccuEnergy Cloud Service (AcuCloud) for Access to Recorded Readings from Any Device Anytime
- ±0.2% Accuracy with ANSI C12.20 Standard for Revenue Grade Meters
AcuView Software for Remote Meter Access and Control, Real-Time Monitoring and Local PC Logging Available for Download
Due to Increased Freight Costs, All AccuEnergy Orders Must Have a Minimum Order Value of $100
Overview of the AccuEnergy Acuvim II Power Meter
The Acuvim II is a versatile high end electrical power meter that can be equipped with data logging capabilities in certain configurations. They are an ideal choice for the monitoring and controlling of power distribution systems. The Acuvim II series provides metering on 400 different parameters as well as Time of Use (TOU) information, and Waveform capture. All monitored data is available via a digital RS484 communication port running Modbus RTU and DNP 3.0 protocols. Additional communication options include Modbus, Ethernet, Profibus DP, and BACnet. The Acuvim II series also utilizes various flexible, modular digital and analog optional I/O modules. Data can be viewed remotely using the free AcuCloud service if equipped with the appropriate communication module. Consult the Acuvim II manual on the “Manuals and Resources” tab to learn more about the great features of this built-to-order power meter.
Acuvim II Models
The Acuvim II series is available in the following configurations.
Acuvim IIR | Acuvim IIW | |
Application | Billing / Data Logging | Power Quality |
Metering | 400 parameters | 400 parameters |
Data Logging | ✔ | ✔ |
Memory | 8MB | 16MB |
Time-of-Use | ✔ | ✔ |
Power Quality | ✔ | |
Waveform Capture | ✔ |
Acuvim II Specifications
Voltage | Range: 20 Volts to 500 kiloVolts Accuracy: 0.2% Resolution: 0.1 Volts |
Current | Range: 5 mA to 50,000 Amps Accuracy: 0.2% Resolution: 0.001 Amps |
Power | Range: -9999 MW to 9999 MW Accuracy: 0.2% Resolution: 1 Watt |
Reactive Power | Range: -9999 MVar to 9999 MVar Accuracy: 0.5% Resolution: 1 Var |
Apparent Power | Range: -9999 MVA to 9999 MVA Accuracy: 0.2% Resolution: 1 VA |
Power Demand | Range: -9999 MW to 9999 MW Accuracy: 0.2% Resolution: 1 W |
Reactive Power Demand | Range: -9999MVar to 9999MVar Accuracy: 0.2% Resolution: 1 Var |
Apparent Power Demand | Range: -9999 MVA to 9999 MVA Accuracy: 0.2% Resolution: 1 VA |
Power Factor | Range: -1.000 to 1.000 Accuracy: 0.2% Resolution: 0.001 |
Frequency | Range: 45.00 Hz to 65.00 Hz Accuracy: 0.2% Resolution: 0.01 Hz |
Energy (Primary) | Range: 0 to 99999999.9 kWh Accuracy: 0.2% Resolution: 0.1 kWh |
Energy (Secondary) | Range: 0 to 999999.999 kWh Accuracy: 0.2% Resolution: 0.001 kWh |
Reactive Energy (Primary) | Range: 0 to 99999999.9 kVarh Accuracy: 0.2% Resolution: 0.1 kvarh |
Reactive Energy (Secondary) | Range: 0 to 999999.999 kVarh Accuracy: 0.2% Resolution: 0.001 kvarh |
Apparent Energy (Primary) | Range: 0 to 99999999.9 kVAh Accuracy: 0.2% Resolution: 0.1 kVAh |
Apparent Energy (Secondary) | Range: 0 to 999999.999 kVAh Accuracy: 0.2% Resolution: 0.001 kVAh |
Harmonics | Range: 0 to 100% Accuracy: 2.0% Resolution: 0.1% |
Phase Angle | Range: 0° to 359.9° Accuracy: 2.0% Resolution: 0.1° |
Unbalance Factor | Range: 0 to 100% Accuracy: 2.0% Resolution: 0.1% |
Running Time | Range: 0 to 9999999.99h Resolution: 0.01h |
Current Inputs (Each Channel) |
Nominal Current: 5A ac Metering Range: 0 to 10 A ac Withstand: 20 Arms (Continuous); 100 Arms (1 Sec., non-recurring) Burden: 0.05VA (typical) @ 5Arms Pickup Current: 0.1% of Nominal Accuracy: 0.2% Full Scale |
Voltage Inputs (Each Channel) |
Nominal Full Scale: 400 Vac L-N, 690 Vac L-L Withstand: 1500Vac (Continuous); 3250 Vac, 50/60 Hz (1 min.) Input Impedance: 2Mohm per phase Metering Frequency: 45 Hz to 65 Hz Pickup Voltage: 30Vac Accuracy: 0.2% Full Scale |
Energy Accuracy | Active: Class 0.2S (According to IEC 62053-22) Reactive: Class 2 (According to IEC 62053-23) |
Harmonic Resolution | Metered Value: 63rd Harmonic |
AC/DC Control Power | Operating Range: 100-415 Vac, 50/60 Hz; 100-300 Vdc Burden: 5W Frequency: 50/60 Hz Withstand: 3250 Vac, 50/60 Hz for 1 Minute Installation Category III (Distribution) |
Low Voltage DC Control Power (Optional) | Operating Range: 20 to 60 Vdc Burden: 5W |
Digital Input (DI) | Input Voltage Range: 20 to 220 Vac/dc Input Current (Max): 2mA Start Voltage: 15 Volts Stop Voltage: 5 Volts Pulse Frequency (Max): 100 Hz, 50% Duty Ratio (5ms ON and 5ms OFF) SOE Resolution: 2 ms |
Digital Output (DO) (Photo-MOS) |
Voltage Range: 0 to 250 Vac/dc Load Current: 100mA (Max) Output Frequency: 25 Hz, 50% Duty Ratio (20ms ON and 20ms OFF) Isolation Voltage: 2500 Vac |
Relay Output (RO) | Switching Voltage: 250 Vac, 30Vdc (Max) Load Current: 5A (R), 2A (L) Set Time: 10ms (Max) Contact Resistance: 30mΩ (Max) Isolation Voltage: 3000 Vac Mechanical Life: 1.5 x 107 |
Analog Output (AO) | Output Range: 0 to 5 Volts; 1 to 5 Volts; 0 to 20mA; 4 to 20mA (Optional) Accuracy: 0.5% Temperature Drift: 50ppm/°C Typical Isolation Voltage: 500 Vdc Open Circuit Voltage: 15 Volts |
Analog Input (AI) | Input Range: 0 to 5 Volts; 1 to 5 Volts; 0 to 20mA; 4 to 20mA (Optional) Accuracy: 0.2% Temperature Drift: 50ppm/°C Typical Isolation Voltage: 500 Vdc |
Power Supply (Digital Input) |
Output Voltage: 24 Volts DC Output Current: 42 mA Load: 21 Digital Inputs (Max) |
Data Storage Capacity | 4MB of Internal Memory for Data Logging |
Communications | RS-485 (Standard); Ethernet, PROFI-BUS (Optional) |
RS-485 Communications | Protocol: MODBUS RTU (Industry Standard) Type: 2 Wire Connection Baud Rate: Up to 38,400 |
Ethernet Communications (Optional) |
10M/100M BaseT MODBUS RTU Protocol Data Browsing Through HTTP Sending E-mail Automatically |
PROFI-BUS Communications (Optional) |
PROFIBUS RTU Protocol Works as PROFIBUS Slave, Baud Rate Adaptive, Up to 12M Typical Input Bytes: 32 Typical Output Bytes: 32 PROFIBUS Standard According to EN 50170 Vol. 2 |
Display | LCD Screen Display with White Back Light Wide Environmental Temperature Endurance Displays Load Percentage, 4 Quandrants Power and Load Nature |
Alarms | Up to 16 Parameters Set with Time Interval Events Recorded with Time Stamps and Triggers Alarm DO Output (44 Different Parameters Available) |
Software Compatibility | Windows 11, 10 and 7 (32 and 64-Bit) |
Operating Range | Temperature: -25°C to 70°C Humidity: 5% to 95% Non-Condensing Pollution Degree: 2 |
Storage Range | Temperature: -40°C to 85°C Humidity: 5% to 95% Non-Condensing |
Standards Compliance | Measurement: IEC 62053-22; ANSI C12.20 Environmental: IEC 60068-2 Safety: IEC 61010-4; UL 61010-1 EMC: IEC 61000-4/-2-3-4-5-6-8-11; CISPR 22 Outlines: DIN 43700; ANSI C39.1 |
Dimensions | 9.6cm x 9.6cm x 5.07cm (3.8" x 3.8" x 2.0") |