Power and Energy Data Logger w/ Display and Sensors
- Supports Single-Phase, Split-Phase, and Three-Phase Electrical Systems
- Power (VA, W, var) & Energy (VAh, Wh, varh) Measurements on 50/60Hz, 400Hz and DC Systems
- LCD Display Shows 3 Inputs
- Supports AC/DC Voltage Measurement Ranges up to 1000 Volts
- Tracks Active, Reactive andApparent Power and Energy
- Logs True RMS Voltage, Current , Watts, VARs, VA and Energy (kWh, kVA)
- Store Measured Current and Voltage Readings onto SD(HC) Cards up to 32 GB
- Bluetooth, USB and Ethernet WiFi LAN and Ethernet/Wi-Fi Direct, Communications Options for Setup and Configuration
- Android App to Connect, Configure, Setup, View Data Using USB, WiFi Direct DataViewSync and Ethernet LAN/WiFi Communications
Includes Tool Bag, (3) MiniFlex MA193-10-BK Current Sensors, USB Cable, (4) 10 ft Black Test Leads w/ (4) Alligator Clips, AC Power Adapter, NiMH AAA 8.4 Volt Battery (12) Color-Coded ID Markers, Multifix Mounting System, Safety Card, 8 GB SD Card and USB-SD Card Reader, USB Memory Stick with User Manual and DataView PC Software
Overview of the AEMC PEL113 Power & Energy Data Logger
The PEL113 is an economically priced, simple to use, single, two, and three phase power/energy data logger. All PEL 100 series loggers offer a full range of essential functions for recording power and energy data from most electrical power networks in use across the world today. The PEL 100 series devices measure and record three True RMS voltage inputs and current inputs, Watts, VARS, VA, and Energy (kWh & kVA). Additionally, Power Factor (PF), Displacement Power Factor (DPF), Crest Factor, Frequency, and Total Harmonic Distortion (THD) are calculated and recorded as well. Individual harmonic percent information from 1 to the 50th harmonic is recorded at the operator’s choice. All variables are recorded and stored at a once second interval and on user selectable demand intervals ranging from 1 to 60 minutes. The PEL 100 series loggers are powered using rechargeable batteries or can be powered directly off the panel when used with the optional 2137.98 power adaptor (sold separately). The PEL 100 series is the perfect choice for electricians, engineers, and contractors performing building and system monitoring and energy audits. The compact design allows the device to be installed inside a load center panel (including the current sensors) allowing the doors to close on most panels.
The PEL113 includes a storage bag, 3 x MiniFlex MA193-10-BK current sensors, 5’ USB cable, four black test leads and alligator clips, power cord, twelve color-coded ID markers, SD-Card with USB reader, and a USB drive containing the DataView software.
AEMC PEL113 Power and Energy Data Logger with LCD Display Specifications
| Inputs | (3) Voltage and (3) Current |
| Types of Installations | Single Phase, Split Phase, 3-Phase, DC, etc (17 Choices) |
| Voltage | Measurement Range (Phase - Neutral): 10 to 1000 Volts AC/DC2 Measurement Range (Phase - Phase): 10 to 1000 Volts AC2 Accuracy: +/-0.2% of Reading + 0.2 Volts |
| Current | Measurement Range (AC): 200 mA to 12 kAAC Measurement Range (DC): 50 mA to 1300 ADC3 Accuracy: +/-0.4% of Reading ± 0.04 Inom |
| Sensors | (3) MiniFlex® MA193-10-BK Sensors (Included) |
| Network Frequency | DC/50/60/400 Hz (VFD/PWM not available) |
| Voltage Ratios | up to 650 kV |
| Current Ratios | N/A with AmpFlex®/MiniFlex® Sensors |
| Power (P, P+, Punb, Qf, N, D, S) | up to 10 GW/Gvar/GVA5 |
| Energy | up to 4EWh/EVAh/Evarh5 |
| Phase | cos φ, tan Φ, PF |
| Phase Order Phasor Diagram |
Yes (with DataView® or App for Android) |
| Harmonics | THD for V, A and harmonics to 50th order for V, A |
| Aggregations (Fixed) | 200 ms/1 s trends |
| Aggregations (Selectable) | 1 to 60 min (12 choices) |
| Min/Max Values | Yes |
| Alarms | Up to 32 Separate Alarms |
| Emailed Reports | Yes, Alarms and Periodical Min/Max Data Through DataViewSync® |
| Storage Media | SD Card (32 GB Max) |
| Recording Length | Several Weeks to Years (Configuration Dependent) |
| Communication | USB, Ethernet Wi-Fi LAN, Ethernet/Wi-Fi Direct, DataViewSync® |
| Software | DataView® (Windows and Android App) |
| OS Compatibility | Android and Windows 11, 10 and 7 (32 and 64 Bit) |
| NEC Article 220.87 Load Study Compliant |
Yes, DataView® Configuration Button and Report Templates |
| Mounting | Embedded Magnets in Case |
| Powered From Phase Voltage | Phase Power Adapter (#2137.90) |
| External Power Supply | 120 / 240 V Line Power Cord |
| Standards Compliance | CE, IP54 / IP20, 1000 Volt CAT III, 600 Volt CAT IV |
| Weight | 1000g (2.2 lbs) |