PowerScout HD 48 Multi-Circuit Power Submeter

Dent Instruments Revenue-Grade Single-Point Energy Measurement Device
SKU
PS48HD-C-D-N
$2,730.00
  • Designed to Monitor Multiple Independent Loads without Purchasing, Mounting, Wiring or Commissioning Individual Energy Meters
  • Monitor Voltage, Current, Power, Energy and Many Electrical Parameters on Single or 3-Phase Systems
  • Connect up to 48 Split-Core or RoCoil Rogowski-Style CTs (Sold Separately)
  • BACnet and Modbus Protocols with Positive and Negative Objects for Net Metering Projects
  • Patented PhaseChek™ LED Indicators Guarantee Correct CT Orientation
  • Line-Powered 90 to 600 Volt Phase-Phase Power Supply
  • Pulse Outputs Rated at 5mA Max Current/40V Max Open Voltage
  • 5 Volt DC, 200 mA Output for Powering Other Devices (Radio or Gateway)
  • Includes Viewpoint Software on USB Flash Drive

Available with Enclosure, Mounting Plate or Display

Current Transformers (CTs) Sold Separately
Special order - please allow 5-7 business days for this item to ship.

Overview of the Dent Instruments PowerScout 48 HD Submeter

The Dent Instruments PowerScout 48 HD is a Multi-Circuit Power Submeter that offers maximum flexibility and versatility. This multi-channel instrument can be configured to monitor multiple electrical circuits simultaneously. It can be used with any of Dent’s split-core, solid-core, or the easy to install RoCoil (Rogowski) current transformers. The PS48HD can monitor any combination of up to 16 three-phase or 48 single-phase electrical devices. The meter provides data updates every second and offers ANSI C12.20-210 Class 0.2 revenue grade accuracy when used with the proper CT. The PowerScout is perfect for data center monitoring, tenant submetering, as well as accountability metering in commercial, retail, and industrial facilities.

The PowerScout HD series of meters are not designed to be standalone energy recorders. They need to be connected as a slave device to a data logger, Remote Terminal Unit (RTU), or a building management host network.

Dent Instruments PowerScout 48 HD Revenue-Grade Networked Power Meter Specifications

Service Type Single Phase, Split Phase, 3 Phase - 4 Wire (WYE), 3 Phase - 3 Wire (Delta)
Voltage Channels 90 to 346 Volts AC Line-to-Neutral, 600 Volts Line-to-Line, CAT III
2 Voltage Reference Inputs
Current Channels 48 Channels: 0.525 Volts AC Max, 333 mV CTs, 0 to 4000 Amp Range Depending on Current Transducer
Maximum Current Input 150% of Current Transducer Rating (mV CTs) to maintain accuracy. Measure up to 4000 Amps with RoCoil CTs
Measurement Type True RMS Using High-Speed Digital Signal Processing (DSP) with Continuous Sampling
Line Frequency 50/60 Hz
Power From L1 Phase to L2 Phase, 90 - 600 Volts AC, RMS CAT III 50/60 Hz, 500mA AC Max.
Use of 12 Volt Auxillary Output Requires 100 Volts AC minimum Input Voltage
AC Protection 0.5A Fuse 20kA Interrupt Capacity
Power Out Unregulated 12 Volts DC Output, 200 mA, Self-Resetting Fuse
WaveForm Sampling 1.8 kHz
Parameter Update Rate 1 Second
Measurements Volts, Amps, kW, kVAR, kVA, aPF, dPF, kW demand, kVA demand, kVA deman, Import (Received) kWh, Export (Delivered) kWh, Net kWh, Import (Received) kVAh, Export (Delivered) kVAh, Net kVAh, Import (Received) kVARh, Export (Delivered) kVARh, Net KVARh, THD, Theta, Frequency. All Parameters for Each Phase and System Total.
Accuracy 0.2% (<0.1% typical) ANSI C12.20-2010 Class 0.2
Resolution Values Reported in IEEE-754 Single Precision Floating Point Format (32-Bit)
Indicators 4-line Display, Tri-color Backlight (PhaseCheck™)
Pulse Output Open Collector, 5mA Max Current, 40 Volts Max Open Voltage
Alarm Output Voltage Phase Loss Alarm (SPDT Relay - 30 Volts DC)
Communications Hardware: RS-485, Ethernet & USB (for Configuration Only)
Supported Protocols: Modbus RTU or BACnet Master Slave Token Passing Protocol (MS/TP); Modbus (using SunSpec IEEE-754 Single Precision Floating Point Model)
Max Distance: 1200 Meters with Data Range of 100K bits/second or Less
RS-485 Loading: 1/8 Unit
Modbus Communication Rate (baud): 9600 (Default), 19200, 38400, 57600, 76800, 115200
BACnet Communication Rate (baud): 9600 (Default), 19200, 38400, 76800
Data Bits: 8
Parity None, Even, Odd
Stop Bit 2, 1
Termination None Provided
Data Formats Modbus, BACnet MS/TP. Modbus TCP or BACnet IP
Wire Connections 12 to 22 AWG 600 Volts AC, Voltage Connection must be #14 AWG or Larger & 600 Volts AC Rated.
Mounting Enclosure or Panel Mount
High Voltage Cover IP40
Mounting Plate Yes
Operating Environment Temperature: -20 to 60°C (-4°F to 140°F)
Humidity: 5 to 95% RH (Non-condensing)
OS Compatibility Windows 11, 10 and 7 (32 and 64 Bit)
Enclosure ABS Plastic, 94-V0 Flammability Rating, Connections Sized for 1-inch EMT conduit
Compliance Standards CE, UL (Conforms to Std. 61010-1)
Weight 340 grams (12 ounces) - Excluding CTs
Dimensions 33.7cm x 25.2cm x 8.0cm (13.3" x 10" x 3.1")
Customer Questions
what is the hd48 voltage input?
The voltage input on the device is from 90 to 346 Volts AC Line-to-Neutral or 600 Volts Line-to-Line. Power for the device is from L1 Phase to L2 Phase, 90 – 600 Volts AC, RMS CAT III 50/60 Hz, 500mA AC Max.