Sensaphone SCD-1200-SD Sentinel Monitoring System Specifications
Inputs
Number: 12 Universal NO / NC: Normally Open / Normally Closed Dry Contact Type: 2.8K Thermistor, 10K Thermistor, 4-20mA Current Loop, Pulse Count Resolution: 12 bits
Temperature
Measurement Range: -85°C to 76°C (-109°F to 168°F)
Output Relay
Type: (1) Low Voltage NO/NC Relay Output Alarm Switching: Manual or Automatic Rated: 1 Amp 30 Volts AC/ 1 Amp 30 Volts DC Programmable
Data Logging
Storage: Unlimited Samples Securely Stored on Sentinel Servers Sampling Interval: 1 Minute to 24 Hours User Programmable Channel Selection
Remote Access
Website or Mobile App to Access Status, Programming, Configuration, Settings
LED Indicators
12 LEDs for Alarm Status, Power Status, Online Status, Relay Output Status and Cellular Link
Alarm Notifications
Unlimited Number of Email, Text or Phone Calls Programmable Alarm Escalation Levels Comprehensive Scheduling per Input, Profile and Alarm Destination Unlimited Number of User Profiles Multiple Contact Types per User
Communication Port
Ethernet 10/100 Base-T
Power Supply
AC Adapter: 90 to 260 Volts AC/7.5 Volts DC 50/60 Hz 7.5 Watt Wall Plug-in Transformer with 6 ft Cord (Included) Power Consumption: 2.6 Watts Power Protection: Metal Oxide Varistor/td>
Battery Backup
8-Hour 4.8 Volt 2000mAHr NiMh Rechargeable Battery Backup in the Event of a Power Outage
Operating Environment
Temperature: 0°C to 50°C (32°F to 122°F) Humidity: 0 to 90% RH, Non-Condensing
Storage Environment
Temperature: 0°C to 50°C (32°F to 122°F) Humidity: 0 to 90% RH, Non-Condensing
Enclosure
Durable Powder Coated Metal Housing Suitable for Wall or Panel Installation or Weatherproof NEMA 4X Rated Fiberglass Enclosure
Standards Compliance
FCC Part 15 Class A
Weight
Weatherproof Enclosure: 3.7 lbs (1.67 kg)
Dimensions
Weatherproof Enclosure: 309mm x 260mm x 89mm (12.17" x 10.25" x 3.50")